PROFIBUS Cable, Connectors, Measuring Points & Repeaters

The right infrastructure makes the difference between quick troubleshooting and hours of downtime. PROFIBUS networks need more than just devices and cable—they need measuring points for diagnostic access, proper connectors for reliable termination, and quality cable that withstands industrial environments.

PROFIBUS

Find the Right Accessories

Additional Accessories

PROFIBUS Stripping Tool

Precision cable stripper designed specifically for PROFIBUS cable construction. Removes jacket and insulation without damaging conductors or shield.

Why it matters: Standard wire strippers can nick conductors or damage the foil shield, causing intermittent failures that are difficult to diagnose. Proper stripping tool ensures clean, reliable connections.

View Stripping Tool →

PROFIBUS Wireless Solutions

Wireless bridges for PROFIBUS communication where cable runs are impractical—mobile equipment, rotating machinery, cross-aisle connections.

Applications: AGVs, rotating tables, conveyor systems, temporary connections, hazardous area crossings. Maintains PROFIBUS protocol timing across wireless link.

View PROFIBUS Wireless →

Planning Guide

Use this checklist during PROFIBUS network design to ensure you have the right infrastructure for reliable operation and efficient troubleshooting:

For New Installations

  • Measuring points: Install at master PLC, segment ends, and every 10-15 devices
  • Cable type: Solid core for fixed runs, extreme drag-chain for moving equipment
  • Connectors: Diagnostic connectors (with LEDs) at segment ends, standard connectors mid-segment
  • Repeaters: Add when segment length exceeds baud rate limits or need more than 32 devices
  • Spare parts: Stock 2-3 connectors, 50m cable, 1-2 repeaters per network

For Existing Networks (Retrofit)

  • Priority #1: Add measuring points if missing—can't troubleshoot running networks without them
  • Priority #2: Replace plastic connectors with shielded metal versions at segment ends
  • Priority #3: Swap non-compliant cable (wrong impedance, single shield, unshielded)
  • Check: Verify termination at both segment ends (220Ω ±5%)
  • Document: Label all measuring points, repeaters, and segment boundaries

Frequently Asked Questions

Can I use standard Ethernet cable for PROFIBUS?
No. PROFIBUS requires Type A cable with 150Ω impedance per EN 50170. Standard Ethernet cable (Cat5/Cat6) has 100Ω impedance. The impedance mismatch causes signal reflections, resulting in communication errors, retries, and intermittent failures. Always use PROFIBUS-compliant cable—it's not interchangeable with Ethernet.
How many measuring points should I install?
Install measuring points at the master PLC, both segment ends, and every 10-15 devices along the network. For a typical 30-device network, that means 4-5 measuring points total. This provides diagnostic access at segment boundaries and mid-segment locations. Without measuring points, you can't test running networks—most problems only appear under production load.
What's the difference between diagnostic connectors and standard PG connectors?
Both provide termination switching and PG/Service diagnostic access. Diagnostic connectors add LED indicators that show power, data transmission, termination status, and error conditions in real-time. The LEDs save troubleshooting time—you can see termination and reflection issues without connecting test equipment. Use diagnostic connectors at critical points (segment ends, complex junctions). Standard PG connectors work fine for mid-segment devices.
When do I need repeaters?
You need repeaters when: (1) Segment length exceeds the maximum for your baud rate (100m at 12 Mbps, 1,200m at 9.6 kbps), (2) You need more than 32 devices on the network, or (3) You want to isolate segments electrically to block EMI. The MULTIrep X2 extends single segments. The MULTIrep X5 hub creates star topologies for distributing networks across multiple machine areas.
Can I mix Fast Connect and screw terminal connectors on the same network?
Yes. Fast Connect and screw terminal connectors are electrically equivalent—both provide proper termination, shielding, and PG/Service access. Fast Connect speeds up installation (no individual wire stripping), while screw terminals offer flexibility for any cable type and easier field repairs. Many installations use Fast Connect for most connections and keep screw terminal connectors for special situations or repairs.
What accessories should I stock as spares?
Stock these for rapid repairs: 2-3 diagnostic connectors (90° Fast Connect), 2-3 standard connectors, 50-100m of your primary cable type, 1-2 MULTIrep X2 repeaters, 2-3 measuring point adapters (IP20 or IP67 depending on environment), and a stripping tool. Having spares on-site means repairs happen in minutes instead of waiting for parts shipment.

Need help troubleshooting or selecting diagnostic tools?

Our measurement technicians provide on-site and remote diagnostic services. Request technical support or book a network assessment.

Or browse our complete line of PROFIBUS diagnostic tools below. All products ship same-day from Atlanta with free expert support.

Questions? Call +1 (678) 880-6910 or email support@indusolamerica.com