MULTIrep X7 - iRepeater 7x | PROFIBUS DP 7-port repeater 110030011
Networking
ⓘ Please contact us for partner and OEM pricing here.
Extend Your PROFIBUS Network with the Compact MULTIrep X2 Repeater
Using a repeater allows an enlargement of your PROFIBUS network until up to 126 devices and to create higher line lengths depending on the fieldbus transmission speed. Per segment, a maximum of 32 devices (31 + repeater) is acceptable. The MULTIrep produces a voltage signal in two, five or seven directions (depending on the version) and raises the signals to the PROFIBUS standard level.
From the physical point of view the MULTIrep provides up to seven isolated segments. The integrated diagnosis via LED allows for simple troubleshooting in each segment.
Instruction for use
Using the MULTIrep creates up to seven galvanically isolated segments. For the purpose of diagnostic measurements a measuring point should be provided at the beginning and end of every segment. Therefore, the PG interfaces at the 9-pin sub-D plugs can be used as measuring points.
If a segment ends or begins directly at the connections of the repeater, it is necessary to activate the bus terminating resistors at the plugs.
Fieldbus connection and termination
PROFIBUS is connected by a 9 pin sub-D socket (according to PROFIBUS guideline). If the segment ends or starts directly at repeater terminals, bus termination resistors have to be activated directly at the plugs.
MULTIrep X7 Advantages
- Basis for a stable PROFIBUS star structure
- Enables stubs in PROFIBUS
- Isolates sensitive or problematic areas
- Expansions or shutdowns possible during running operation.
- Errors affect only small parts of the network.
Technical Data
- Voltage supply: 24 VDC ±20%
- Power supply: 0,3 A
- Connection: 2-7 x 9-poliger Sub-D
- Baud rate: 9,6 kbps to 12 Mbps
General Data
- Installation: 35 mm DIN top hat rail
- Dimensions (H x W x D): MULTIrep X7 - 105 x 212 x 40 mm
- Protective system: IP20
- Operating temperature: +5 °C to +55 °C
- Storage temperature: -20 °C to +70 °C
- PROFIBUS types: DP, DP-V1, FMS, MPI
- Bus: Status of the fieldbus per channel
- Green: Okay
- Red: Error telegram, telegram repetition, diagnostic message, device failure
- Data:
- Green: Fieldbus activity on the channel
- Red: Configured problems in PROFIBUS
- OFF: No fieldbus activity